The electromagnetic flowmeter works on Faraday’s law: a conductive fluid cutting magnetic field lines generates an induced electromotive force across the electrodes, proportional to flow velocity. The essential requirement is that the medium must be conductive. The MF2 standard version is suitable for conductivity ≥15 µS/cm, and the low‑conductivity version for 1.0 to 15 µS/cm. The value of 1.0 µS/cm is not a marketing figure, but an engineering lower limit for this instrument. So the first question in sizing is not price or diameter, but the actual measured conductivity at the installation point.
Why “low conductivity” is not a marketing claim but an engineering boundary
The lower the conductivity, the weaker the useful signal and the greater the influence of disturbances: electrode polarisation potential, induced noise, and zero instability. The low‑conductivity model employs low‑frequency square‑wave excitation (1/10, 1/16, 1/25, 1/32 of mains frequency) to suppress electrode polarisation and stabilise zero. For media with high solids content, high‑frequency excitation (1/2 mains frequency) and mixed‑frequency excitation are available; the latter can measure slurries with solids concentration up to 78%.
A common misconception is to “choose one size larger” or “increase excitation voltage”. This will not extend the method’s boundary: when conductivity is below the allowable value, such measures only accelerate zero drift and shorten liner life.
True adaptation – not by selecting from a catalogue, but by selecting according to your medium
1.0 µS/cm is a necessary condition, but not sufficient. The next step is to match the medium specifically.
Electrodes: 316L, Hastelloy B/C, titanium, tantalum, Monel, tungsten carbide, platinum, platinum‑iridium alloy. For strongly oxidising media, tantalum and platinum‑iridium are common choices; for alkaline solutions and hydrofluoric acid, Monel; for abrasive media, tungsten carbide.
Linings: PTFE (−80 to +180 °C), PFA (−50 to +180 °C), FEP (−50 to +150 °C), PVDF, ETFE, rubber types, Al₂O₃ ceramic. The sanitary version MF22 uses a 316 stainless steel body with PFA lining.
Structure: In addition to standard electrodes, optional self‑cleaning, scraper, or replaceable electrodes are available for scaling‑prone media.
Electronics: Self‑diagnostics cover empty pipe (no additional electrodes needed), excitation circuit, bubbles, and electrode scaling; three totalisers record forward, reverse, and differential totals.
Accuracy: High‑accuracy version up to 0.2%, standard version 0.5%; flow velocity range 0.3 to 12 m/s.
Assembly and verification are carried out in Beijing, China; the instrument is supplied with a certificate of conformity and verification record.
Applicable and non‑applicable cases
The low‑conductivity version is suitable for conductivity 1.0 to 15 µS/cm: reverse osmosis permeate and deionised water, industrial condensate, pharmaceutical pure water loops, CIP alkaline/acid washes (about 2 to 8 µS/cm), and reagent aqueous solutions.
The following cases are not suitable:
Conductivity below 1.0 µS/cm.
Non‑aqueous media – 96% ethanol, glycerol, most organic solvents and oils – should switch to Coriolis or ultrasonic principles.
Values near the boundary (0.8 to 1.0 µS/cm), e.g. water for injection, must be confirmed by on‑site measurement.
Media containing significant ferromagnetic materials or free gas.
Additional notes: For abrasive particles, recommended velocity 1–3 m/s; for depositing media, 2–5 m/s.
How to select – why start with medium data, not price
Minimum data set for selection: on‑site measured conductivity at operating temperature (not the nameplate value); chemical composition, temperature, pressure, and abrasiveness of the medium; flow range and pipe diameter (check that velocity falls within 0.3–12 m/s); piping layout drawing indicating pumps, valves, and chemical injection points – upstream injection causes non‑uniform conductivity, so the meter should be located away from injection points.
From this, the model, electrode/liner materials, structural design, and accuracy class can be determined. Verifying parameters before ordering is far more cost‑effective than replacing the meter after installation. Technical data and sizing specifications are available at masteryb.ru.
The electromagnetic flowmeter is not a universal solution, but in its applicable field – aqueous media with conductivity above 1.0 µS/cm – it remains one of the most stable options: no moving parts, no pressure loss, and comprehensive self‑diagnostics. Start with conductivity, not price: one on‑site measurement tells you whether the method is applicable and which MF2 configuration to choose.